Aermec's Andy Hawes asks if cooling data centres is more than refrigerant choice

Aermec's Andy Hawes asks if cooling data centres is more than refrigerant choice

Thu, 26th Nov 2026 (Today)
Andy Hawes
ANDY HAWES General Manager Technical Services Aermec UK Limited

As cloud computing, digital services and AI continue to drive demand for data-centre capacity, cooling systems are being assessed against increasingly demanding requirements for efficiency, resilience, safety and regulatory compliance. 

Historically, refrigerants were selected primarily for cooling performance and equipment compatibility. Today, considerations also include regulatory requirements, safety classifications, refrigerant availability, servicing arrangements and whole-life operational objectives. However, no single refrigerant characteristic should be viewed as a standalone indicator of a facility's overall environmental performance.

Because data centres are mission-critical facilities with long operating lifespans, cooling systems must support high availability while minimising disruption. Refrigerant and equipment selection should therefore be based on project-specific requirements, resilience objectives and documented whole-life assumptions.

The regulatory landscape varies by jurisdiction. In the European Union, Regulation (EU) 2024/573 introduced a steeper HFC phase-down, additional equipment restrictions and a phase-out trajectory extending to 2050. Great Britain operates a separate retained F-Gas regime, while Northern Ireland continues to apply relevant EU requirements under the Windsor Framework.

As a result, refrigerant strategy should be based on installation location, equipment category, refrigerant charge, safety requirements and anticipated service life rather than a generic interpretation of F-Gas legislation.

Questions surrounding refrigerant availability, future compliance, operational risk and servicing requirements increasingly influence cooling system design, but their relative importance remains project-specific.

Cooling Architecture

A modern data-centre cooling strategy extends far beyond refrigerant choice. Solutions may include air-cooled and water-cooled chillers, free-cooling systems, glycol-free designs, precision air-conditioning equipment, oil-free centrifugal platforms, screw-compressor chillers, direct expansion systems and indirect evaporative cooling.

The most appropriate architecture depends on factors such as IT load density, climate conditions, resilience philosophy, acoustic constraints, water availability and operational requirements.

Within relevant Aermec data-centre chiller platforms, refrigerant options include R513A, R1234ze(E) and, on selected products, R515B. Availability varies by model, capacity and market and should always be confirmed against current technical data and local regulations.

Examples include:

TBG oil-free air-cooled chillers using R1234ze(E) or R515B, including free-cooling variants.

NSG screw-compressor chillers using R1234ze(E).

WMG water-to-water chillers using R1234ze(E) and oil-free magnetic levitation compressors.

These examples demonstrate why refrigerant selection should be considered alongside compressor technology, operating temperatures, heat-exchanger design, redundancy strategy, free-cooling potential and required cooling capacity.

Comparing R513A and R1234ze(E)

R513A is an HFO/HFC blend with zero ozone-depletion potential and an ASHRAE A1 classification, indicating lower toxicity and no flame propagation under standard test conditions. Its commonly quoted GWP is approximately 630, depending on the assessment methodology used.

Where an A1 refrigerant is required, R513A can provide a practical solution. However, its higher GWP compared with R1234ze(E) should be considered within the project's long-term refrigerant management and regulatory strategy. R1234ze(E) is a single-component HFO refrigerant with zero ozone-depletion potential and a significantly lower GWP. It is classified by ASHRAE as A2L, indicating lower toxicity and lower flammability. On an equivalent mass basis, it has a lower direct refrigerant-emissions impact than R513A.

However, lower GWP alone does not demonstrate lower whole-life environmental impact. Any assessment should also consider refrigerant charge, leakage rates, recovery practices, equipment efficiency, maintenance arrangements and operating conditions.

Because R1234ze(E) is an A2L refrigerant, installations require safeguards determined by equipment design, site-specific risk assessment and applicable standards.

Energy Performance and Reporting

Data-centre operators are increasingly expected to demonstrate energy, emissions and resource performance through regulatory requirements, customer specifications, funding criteria and corporate reporting frameworks.

Cooling systems can contribute significantly to energy-efficiency objectives, but performance claims should identify the equipment selected, operating conditions and calculation methodology. Generalised efficiency claims cannot guarantee project outcomes.

Power Usage Effectiveness (PUE) remains the most widely used measure of overall data-centre energy efficiency. However, PUE is a whole-facility metric and should not be attributed solely to the cooling plant.

Efficient cooling, free cooling, higher chilled-water temperatures and optimised controls can help reduce PUE, but actual results also depend on climate, IT utilisation, electrical infrastructure, redundancy levels and measurement boundaries.

Leakage Management and Safety

Refrigerant leakage contributes to greenhouse-gas emissions according to both the quantity released and the refrigerant's GWP. Effective leak management supports both environmental objectives and regulatory compliance.

Depending on jurisdiction and refrigerant charge, operator responsibilities may include leak prevention, inspections, leak detection systems, record keeping, refrigerant recovery and the use of qualified personnel. These requirements should form part of the maintenance strategy throughout the equipment lifecycle.

For A2L refrigerants such as R1234ze(E), safeguards must be established through both equipment design and project risk assessment. Depending on the installation, these may include refrigerant charge limits, ventilation, leak detection, ignition-source control, emergency procedures, signage, access controls and competent-person training.

Compliance should be assessed against applicable legislation, manufacturer instructions and relevant standards, including EN 378 and EN IEC 60335-2-40 where applicable.

The appropriate refrigerant is determined by customer requirements, operating duty, equipment selection, safety assessment and applicable regulation rather than by a universal preference for a particular option. For UK data-centre projects, R513A may remain attractive where an A1 refrigerant classification is required, while R1234ze(E) may be considered where reducing direct refrigerant-emission potential forms part of the project's objectives and A2L design measures are acceptable. The choice remains project-specific.

Refrigerant selection should not be viewed as a standalone measure of environmental performance or compliance. Data-centre cooling strategies should balance energy efficiency, resilience, safety, maintainability, regulatory exposure and whole-life cost. 

The most effective solution is a verified combination of refrigerant, compressor technology, heat-rejection method, free-cooling strategy, controls and redundancy, tailored to the specific requirements of the site and customer.